State Grid pilots first broadband measurement device in Jiaxing
On Sept 22, State Grid Corporation of China successfully launched its first broadband voltage/current measurement device at the 110-kilovolt Shimen Substation in Tongxiang, Jiaxing city, Zhejiang province. The trial marks a breakthrough in the company's key technology research project on broadband voltage/current measurement and its digital applications.
The Shimen Substation, with its open layout, extensive photovoltaic integration, and stable transformer load, provided an ideal installation site and operating environment for the pilot device. The system consists of primary and secondary equipment: three primary units are installed outdoors, while one secondary cabinet is housed in the substation's control room, forming an integrated monitoring and analysis framework.
With the rapid expansion of renewable energy integration and high-voltage direct current projects, power electronic equipment has been widely applied to the grid, injecting large amounts of interharmonic and high-order harmonic signals. Existing measurement and control systems, however, remain largely focused on power-frequency signals, unable to meet the advanced monitoring needs.
Developed over three years of R&D and testing, the broadband measurement device's core advantage lies in its ability to capture "abnormal signals" in real-time. It can accurately measure high-order harmonics, power-frequency and transient signals, feeding data directly into dispatching systems. This capability enhances grid fault location, harmonic management, equipment condition assessment, and intelligent operation and maintenance, providing vital support for the creation of a smarter, more resilient power system.
The device offers unprecedented precision: power-frequency measurement accuracy of 0.02 percent; harmonic response amplitude error below 1.5 percent within 3,000 Hz; a response time to a 5-nanosecond square wave of 300 nanoseconds; and a measurement frequency extending up to 1 MHz. These performance levels far surpass conventional devices, significantly boosting observability and digitalization of the regional grid.
According to project engineer Zhao Yuheng, the device also achieves "one-to-many" functionality — combining measurements of primary current, voltage, power-frequency, transient signals, harmonics, and lightning impulses into a single unit. This reduces installation redundancy, saves space, and ensures compatibility with protection systems and harmonic monitoring platforms, offering broad application prospects.
To ensure safe installation, operation crews carried out load-shedding and switching procedures in advance, creating a secure working environment. Construction tasks — including the installation of new transformer supports, secondary cable laying and simulation testing — were completed in phases to minimize impact on grid operations.
State Grid Jiaxing Power Supply Company will continue operating and analyzing the broadband device, further integrating it with artificial intelligence, big data and machine learning. The company aims to develop replicable and scalable experiences, advancing grid modernization and high-quality development through technological innovation.